Grounding of DCS control system of air separation plant

Grounding of DCS control system of air separation plant
Nov 25, 2024
Author: DEAR AST
Question Reply

In the operation of air separation plant, in order to ensure the accuracy of DCS control system monitoring and the safety and stability of operation, it is necessary to do well of DCS system grounding.

 

Grounding is to connect the circuit and unit with an equipotential or equipotential surface as the common reference point of signal to realize low impedance value, so as to ensure that when the signal, power supply or DCS system equipment entering DCS system is abnormal, it can bear overload current and quickly lead the overload current to the earth, provide shielding layer for DCS system, eliminate electronic noise interference, and provide the whole control system with a shielding layer The system provides reference zero potential of common signal.

 

The grounding of DCS control system shall follow the following principles:

 

1.The logic grounding, signal grounding and shielding grounding in DCS system shall meet the requirements of "one point grounding". Insulated copper stranded wire or cable shall be used to connect to the general grounding copper bar.

 

2.The DCS system shall be insulated from the foundation by installing insulation pads and insulation bolts, and the insulation resistance to ground shall be greater than 50m Ω.

 

3.When the insulation between power supply cabinet, operation console, relay cabinet and foundation is uncertain, they shall not be connected to the general grounding copper bar, but shall be connected to the nearby indoor electrical protection grounding trunk line.

 

4.When selecting the access point of DCS system for public grounding grid, the grounding resistance of common grounding grid shall not be greater than 4 Ω, and the connection resistance shall not be greater than 1 Ω, and the access point of DCS shall be far away from the current entry point.

 

5.The shielding layer of DCS system signal shielding cable shall not float in the air and must be grounded.

DEAR Air Separation Solve YourGrounding of DCS control system of air separation plantYou can also learn about otherLarge air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Its essence is to seek the optimal balance between the "lower tower separation effect" and the "upper tower feed quality". Liquid air serves as the bottom product of the lower tower and also as the feed for the upper tower. If the oxygen content is below 36%, it indicates that the reflux ratio of the lower tower is too high, and there is too much nitrogen in the liquid air. After entering the upper tower, it increases the separation burden of the distillation section, resulting in a decrease in oxygen extraction rate; If the oxygen content is higher than 40%, it reflects insufficient separation in the lower tower, often accompanied by a synchronous decrease in liquid nitrogen purity, and an imbalance in load distribution between the upper tower distillation and extraction sections, affecting the quality of nitrogen gas at the top. The raw air contains about 21% oxygen and is initially distilled and concentrated to 36% to 40% in the lower tower, which is the cost-effective balance point
2026.11.27
The purity of liquid air and liquid nitrogen is the core indicator for the operation of air separation distillation tower, which directly determines the quality of subsequent oxygen and nitrogen products. Controlling purity requires a systematic approach from three aspects: distillation conditions, cooling balance, and operating parameters. Firstly, stabilizing the pressure and temperature of the distillation tower is fundamental. Pressure fluctuations in the lower tower can cause gas-liquid equilibrium drift, resulting in changes in liquid air purity. The lower tower pressure should be maintained near the design value to avoid significant fluctuations; Simultaneously monitor the temperature difference of the main condenser evaporator. If the temperature difference is too large, it indicates insufficient liquid nitrogen purity or abnormal liquid oxygen level. Secondly, control the reflux ratio reasonably. The ratio of liquid nitrogen reflux rate to rising gas volume determines the dist
2026.11.26
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top