Grounding of DCS control system of air separation plant

Grounding of DCS control system of air separation plant
Nov 25, 2024
Author: DEAR AST
Question Reply

In the operation of air separation plant, in order to ensure the accuracy of DCS control system monitoring and the safety and stability of operation, it is necessary to do well of DCS system grounding.

 

Grounding is to connect the circuit and unit with an equipotential or equipotential surface as the common reference point of signal to realize low impedance value, so as to ensure that when the signal, power supply or DCS system equipment entering DCS system is abnormal, it can bear overload current and quickly lead the overload current to the earth, provide shielding layer for DCS system, eliminate electronic noise interference, and provide the whole control system with a shielding layer The system provides reference zero potential of common signal.

 

The grounding of DCS control system shall follow the following principles:

 

1.The logic grounding, signal grounding and shielding grounding in DCS system shall meet the requirements of "one point grounding". Insulated copper stranded wire or cable shall be used to connect to the general grounding copper bar.

 

2.The DCS system shall be insulated from the foundation by installing insulation pads and insulation bolts, and the insulation resistance to ground shall be greater than 50m Ω.

 

3.When the insulation between power supply cabinet, operation console, relay cabinet and foundation is uncertain, they shall not be connected to the general grounding copper bar, but shall be connected to the nearby indoor electrical protection grounding trunk line.

 

4.When selecting the access point of DCS system for public grounding grid, the grounding resistance of common grounding grid shall not be greater than 4 Ω, and the connection resistance shall not be greater than 1 Ω, and the access point of DCS shall be far away from the current entry point.

 

5.The shielding layer of DCS system signal shielding cable shall not float in the air and must be grounded.

DEAR Air Separation Solve YourGrounding of DCS control system of air separation plantYou can also learn about otherLarge air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
What's the reason for using two-stage distillation column in air separation column?Usually, the air in the lower column is pre separated by the air separation column, which is rectified into liquid air which is rich in oxygen and pure nitrogen, and then further rectified in the upper column to obtain oxygen and nitrogen products. The connection between the upper and lower columns is the condensing evaporator. It uses the pressured nitrogen of the lower column to heat the liquid oxygen in the upper column, so as to evaporate the liquid oxygen while condensing the liquid nitrogen. The advantage of using two-stage distillation column is that the product has high extraction rate, and high purity oxygen and nitrogen can be obtained at the same time. Oxygen and nitrogen products can also be produced in a single-stage distillation column, but only one product can be produced separately. It is similar to the lower column of two-stage distillation column, in which pure nitrogen product can be
2026.11.17
Answer: to judge whether the air separation unit is advanced or not, it mainly depends on three hard indicators, combined with the comprehensive evaluation of the intelligent level. 1. Core evaluation index -Unit power consumption: commonly measured in kwh/nm ³ o ɑ, it is the operating cost index that customers are most concerned about; The larger the scale and the higher the purity, the lower the unit energy consumption. -Oxygen extraction rate: it reflects the utilization efficiency of raw air. The higher the extraction rate, the more electricity is saved. The cryogenic method is usually better than the simple process. -Operation stability and load regulation range: whether the load can be changed smoothly between 30% and 110% will directly affect the ability of adaptive gas fluctuation. 2. Embodiment of the advanced nature of Deere air separation -The eighth generation of intelligent air separation technology: make system optimization in process organization and equipment matching,
2026.11.16
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top