Air cooling towerIf the automatic adjustment system of the liquid level fails, it is easy to cause the water inflow accident of the air separation tower, so the reliability of the self-adjustment system of the liquid level must be improved. Attention should be paid when installing:
1) the differential pressure transmitter should be installed on the same standard level as the bottom of the air cooling tower;
2) positive pressure and negative pressure diversion pipes should be introduced into differential pressure transmitter on the same horizontal plane;
3) in winter, heating and antifreezing measures should be taken to prevent the static water in the diversion pipe from freezing.
In order to improve its working stability and accuracy, a standard liquid level container can be installed in the negative pressure lead-out pipe. In the standard liquid level container, the height H of the liquid level is maintained constant by supplementary water and overflow pipe, which is generally consistent with the highest liquid level in the tower. In this way, both the positive and negative pressure chamber of the pneumatic differential pressure transmitter can enter water at the same time, eliminating the measurement error caused by the small amount of water in the original negative pressure tube (air pipe. The pressure felt by the negative pressure chamber is constant (= & rho; gHo, & rho; is the density of water), and its output signal is proportional to the liquid level height of the air cooling tower day by day: △p = & rho; g (H-Ho ). After adopting the standard liquid level container, the use effect is very good, the work is stable and reliable, and the automatic adjustment is guaranteed.

DEAR Air Separation Solve YourHow to ensure the normal operation of the automatic liquid level adjustment system of the air cooling tower?You can also learn about otherLiquefied air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Its essence is to seek the optimal balance between the "lower tower separation effect" and the "upper tower feed quality". Liquid air serves as the bottom product of the lower tower and also as the feed for the upper tower. If the oxygen content is below 36%, it indicates that the reflux ratio of the lower tower is too high, and there is too much nitrogen in the liquid air. After entering the upper tower, it increases the separation burden of the distillation section, resulting in a decrease in oxygen extraction rate; If the oxygen content is higher than 40%, it reflects insufficient separation in the lower tower, often accompanied by a synchronous decrease in liquid nitrogen purity, and an imbalance in load distribution between the upper tower distillation and extraction sections, affecting the quality of nitrogen gas at the top. The raw air contains about 21% oxygen and is initially distilled and concentrated to 36% to 40% in the lower tower, which is the cost-effective balance point
2026.11.27
The purity of liquid air and liquid nitrogen is the core indicator for the operation of air separation distillation tower, which directly determines the quality of subsequent oxygen and nitrogen products. Controlling purity requires a systematic approach from three aspects: distillation conditions, cooling balance, and operating parameters. Firstly, stabilizing the pressure and temperature of the distillation tower is fundamental. Pressure fluctuations in the lower tower can cause gas-liquid equilibrium drift, resulting in changes in liquid air purity. The lower tower pressure should be maintained near the design value to avoid significant fluctuations; Simultaneously monitor the temperature difference of the main condenser evaporator. If the temperature difference is too large, it indicates insufficient liquid nitrogen purity or abnormal liquid oxygen level. Secondly, control the reflux ratio reasonably. The ratio of liquid nitrogen reflux rate to rising gas volume determines the dist
2026.11.26
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top