Liquid oxygen is a strong combustion supporting substance, and its pressure is very high during gasification and bottle filling, so special safety measures should be taken during system configuration:

1) The liquid inlet pipe and gas return pipe connected between the pump and the storage tank shall be equipped with emergency shut-off valves, which shall be interlocked with the pump, so that in case of an accident, the liquid and gas sources can be cut off from a long distance in time, and the liquid pump can be stopped in an emergency;

2) The outlet of liquid oxygen pump shall be equipped with overpressure alarm and interlock pump stop device;

3) The oxygen header behind the high-pressure vaporizer shall be equipped with temperature indication and temperature alarm devices to prevent liquid oxygen from entering the cylinder and causing accidents;

4) Steel plates with a thickness of more than 5mm shall be set around the liquid oxygen pump to form a protective separation wall;

5) The shaft seal of liquid oxygen pump shall be equipped with nitrogen protection gas pipe;

6) The filling manifold shall be filled with a new type of metal hose with anti misplacement connector, and it is strictly prohibited to use hoses made of other materials. High pressure valves and pipelines shall be provided with O-ring made of copper wire;

7) The busbar shall be connected with an overpressure audible and visual alarm device;

8) The number of bottles filled in the manifold is determined by the filling volume and filling speed of the pump to prevent excessive flow rate.

DEAR Air Separation is familiar with the principle of equipment. Professional training instructors escort customers. How to let customers get familiar with the equipment as soon as possible is crucial to ensure correct and reasonable operation.

DEAR Air Separation Solve YourWhat safety problems should be paid attention to in low-temperature liquid oxygen gasification and filling systemYou can also learn about otherAir separation parts FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
The amount of liquid nitrogen removed from the lower column of the air separation unit will affect the purity of the liquid nitrogen in the lower column and the oxygen enriched liquid air at the bottom of the column. When the liquid nitrogen removal amount of the lower column increases, the reflux liquid participating in the heat and mass exchange of the lower column will be reduced, the temperature rise of the rising steam on the column plate will be correspondingly reduced, the condensation of the rising steam will not be sufficient, the oxygen component will be condensed less, the purity of nitrogen at the column top will be reduced, and the purity of liquid nitrogen will be naturally reduced. At the same time, the temperature rise of the downflow liquid will increase, the liquid evaporation will be more sufficient, more nitrogen components will be evaporated to the top of the column, and the purity of the liquid air at the bottom of the column will be improved accordingly.
2026.01.23
What is the function of oil cooler of air separation equipment?
2026.01.22
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top