What safety problems should be paid attention to in low-temperature liquid oxygen gasification and filling system

What safety problems should be paid attention to in low-temperature liquid oxygen gasification and filling system
Dec 13, 2022
Author: DEAR AST

Liquid oxygen is a strong combustion supporting substance, and its pressure is very high during gasification and bottle filling, so special safety measures should be taken during system configuration:

1) The liquid inlet pipe and gas return pipe connected between the pump and the storage tank shall be equipped with emergency shut-off valves, which shall be interlocked with the pump, so that in case of an accident, the liquid and gas sources can be cut off from a long distance in time, and the liquid pump can be stopped in an emergency;

2) The outlet of liquid oxygen pump shall be equipped with overpressure alarm and interlock pump stop device;

3) The oxygen header behind the high-pressure vaporizer shall be equipped with temperature indication and temperature alarm devices to prevent liquid oxygen from entering the cylinder and causing accidents;

4) Steel plates with a thickness of more than 5mm shall be set around the liquid oxygen pump to form a protective separation wall;

5) The shaft seal of liquid oxygen pump shall be equipped with nitrogen protection gas pipe;

6) The filling manifold shall be filled with a new type of metal hose with anti misplacement connector, and it is strictly prohibited to use hoses made of other materials. High pressure valves and pipelines shall be provided with O-ring made of copper wire;

7) The busbar shall be connected with an overpressure audible and visual alarm device;

8) The number of bottles filled in the manifold is determined by the filling volume and filling speed of the pump to prevent excessive flow rate.

DEAR Air Separation is familiar with the principle of equipment. Professional training instructors escort customers. How to let customers get familiar with the equipment as soon as possible is crucial to ensure correct and reasonable operation.

DEAR Air Separation Solve YourWhat safety problems should be paid attention to in low-temperature liquid oxygen gasification and filling systemYou can also learn about otherAir separation parts FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
The purity of liquid air and liquid nitrogen is the core indicator for the operation of air separation distillation tower, which directly determines the quality of subsequent oxygen and nitrogen products. Controlling purity requires a systematic approach from three aspects: distillation conditions, cooling balance, and operating parameters. Firstly, stabilizing the pressure and temperature of the distillation tower is fundamental. Pressure fluctuations in the lower tower can cause gas-liquid equilibrium drift, resulting in changes in liquid air purity. The lower tower pressure should be maintained near the design value to avoid significant fluctuations; Simultaneously monitor the temperature difference of the main condenser evaporator. If the temperature difference is too large, it indicates insufficient liquid nitrogen purity or abnormal liquid oxygen level. Secondly, control the reflux ratio reasonably. The ratio of liquid nitrogen reflux rate to rising gas volume determines the dist
2026.11.26
An argon tower is added to the air separation unit to extract crude argon. The main tower is the source of argon components. Its structure and working condition stability directly affect the operation of the argon tower, and there are strict requirements for the design and operation of the main tower. The argon content in the air is about 0.932%, which is mainly concentrated at the argon fraction extraction port in the middle of the upper tower. The upper column of the main tower shall have enough theoretical plates to ensure the preliminary separation of oxygen, nitrogen and argon and produce stable argon fraction. If the separation efficiency of the tray is poor and the oxygen and nitrogen impurities in the argon fraction fluctuate greatly, the argon tower load will be increased and the working condition of the argon tower will be disordered. The argon fraction extraction port should be precisely set in the area with the highest argon concentration in the upper column, and the oxygen
2026.11.25
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top