Liquid air separation plant temperature measurement instrument common failures

Liquid air separation plant temperature measurement instrument common failures
Jun 10, 2022
Author: DEAR AST

Thermocouple thermometer common fault for the indication of low value, or stop at zero. This is due to the thermocouple generated problems, may be poor contact or broken circuit, generally do not appear to indicate the phenomenon of high.
In order to ensure the measurement accuracy, the use of the cold end of the temperature compensation should be correct (commonly used compensation wire method), and pay attention to the thermal electrode and the earth between a good insulation.
RTD thermometer common fault: sometimes the pointer always points to the maximum. This is a resistance thermometer temperature measurement element break, so that the resistance of infinity, or poor contact between the two ends, contact resistance; another phenomenon is the pointer pointing to zero, or deflected to the negative direction. The reason is a short circuit in the temperature measuring element, resistance to zero, or due to the resistance thermometer protection casing leakage or icing caused by; there is another phenomenon is the pointer does not move, which is due to the bridge itself out of the problem, not working caused by.
In use to strictly prevent moisture into the RTD protection tube, after the display meter must not be open or short-circuit. In the inspection of the RTD, the measurement current should not be greater than 5mA.

Translated with www.DeepL.com/Translator (free version)

DEAR Air Separation Solve YourLiquid air separation plant temperature measurement instrument common failuresYou can also learn about otherLiquefied air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Generally, the actual cooling capacity of expander is always less than the theoretical cooling capacity. Under the same inlet and outlet pressure and inlet gas temperature, the lower the efficiency of expander, the smaller the unit refrigerant cooling capacity and the smaller the temperature drop efficiency of expander. The efficiency of expander depends on the size of various losses inside the expander. Due to the existence of various losses, the ability of gas to do external work is reduced in varying degrees. To sum up, the losses mainly include the following aspects: 1. When the air flow passes through the work wheel and the deflector, the loss caused by friction and air flow impact on the runner surface is called flow loss. 2. When the impeller is rotating, the friction heat generated by the gas around the wheel disc will increase the temperature of the gas, which is called friction blast loss. 3. When the gas passes through the deflector, the leakage from the gap bet
2025.11.07
The principle and function of molecular sieve purification system in air separation equipment?
2025.11.06
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top