Air separation plant is an important supporting facility for large-scale industrial enterprises, such as chemical industry, smelting industry, electronics industry and energy industry. Its operation condition is very important to the enterprise. In the actual production, the air separation plant is often be shut down by mistake due to many factors, such as instrument control incorrect interlocking, manual incorrect operation or network voltage fluctuation, which causes great losses to the enterprise. Here are a few preventive measures for incorrect shutdown.

 

1.Prevention of instrument and control system incorrect interlock: the common factors that causeinstrument and control system incorrect interlock include alternating magnetic field interference, detection component failure and unreasonable interlock parameter setting, etc.

 

a.In order to reduce the influence of alternating magnetic field on the signal of I & C system, when installing and using large electrical plant, welding machine, interphone and remote control device of plant, it should bekeptaway from the measuring elements of I & C, and regularly test the shielding and grounding performance of I & C cable.

 

b.Through the modification of the interlock, the interlock parameters should beset reasonably. The reliability of the instrument and control elements is enhanced, and the incorrect interlock shutdown caused by the failure of a single measuring element is avoided.

 

2.Prevention of manual misoperation: the common forms of manual misoperation include data input error, improper operation procedures in emergency state, misoperation of safety protection facilities, unconscious misoperation, etc. In order to prevent the occurrence of manual misoperation, the operation authority and scope shall be set at the key control points, and good operation habits shall be formed. Specifically, the programmed operation can be carried out through the preparation of post operation procedure card and process post emergency response card and other measures. In addition, it is necessary to carry out joint security system for post employees to strengthen their safety responsibility awareness.

 

3.Disturbance of networkvoltage fluctuation factor to plant: to minimize grid "sloshing point"for the interference of mechanical and electrical plant, the time relay with reset terminal can be adopted. In the moment of sloshing, when the speed of main motor has not decreased with the help of inertia, the voltage will return to normal, and the original main motor will be automatically reset and started.

 

In order to prevent the air separation plant from incorrect shutdown, it is necessary to start from many aspects such as the change of staff awareness, the improvement of skills, the refinement of plant management and the improvement of the stability of control system, so as to extend the continuous operation cycle of air separation plant and reduce the production and operation costs.

DEAR Air Separation Solve YourPrevention of incorrect shutdown of air separation plantYou can also learn about otherLarge air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Generally, the actual cooling capacity of expander is always less than the theoretical cooling capacity. Under the same inlet and outlet pressure and inlet gas temperature, the lower the efficiency of expander, the smaller the unit refrigerant cooling capacity and the smaller the temperature drop efficiency of expander. The efficiency of expander depends on the size of various losses inside the expander. Due to the existence of various losses, the ability of gas to do external work is reduced in varying degrees. To sum up, the losses mainly include the following aspects: 1. When the air flow passes through the work wheel and the deflector, the loss caused by friction and air flow impact on the runner surface is called flow loss. 2. When the impeller is rotating, the friction heat generated by the gas around the wheel disc will increase the temperature of the gas, which is called friction blast loss. 3. When the gas passes through the deflector, the leakage from the gap bet
2025.11.07
The principle and function of molecular sieve purification system in air separation equipment?
2025.11.06
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top