For low-pressure air separation devices, the absolute pressure of compressed air discharged from the air compressor is around 0.6MPa. After compression, the moisture content per unit volume of air increases, causing its moisture content to reach the saturation level corresponding to the temperature at that time. When air flows through the air cooling tower, as the temperature decreases, the corresponding saturated moisture content decreases, and the excess part will precipitate from the gas in a liquid state. This portion of water vapor condenses into water, while releasing latent heat of condensation, which not only increases the cooling water volume but also increases the water temperature. But the temperature of the air exiting the tower decreases, so although the air comes into direct contact with water in the cooling tower, its moisture content will actually decrease.
For example, for a 3200m3/h oxygen generator, the processing air volume is 19580m3/h, and the absolute pressure of compressed air is 0.59MPa. The temperature of the air entering the air cooling tower is 50 ℃, and the temperature of the air exiting the air cooling tower is 30 ℃. In this case, the amount of water released by the air passing through the cooling tower can reach 220kg/h.
Kaifeng DEAR Air Separation is deeply rooted and practiced in the field of air separation research. It specializes in the research and development, manufacturing, and installation of various complete sets of air separation equipment, and is good at providing customers with the most competitive air separation project design solutions. It has been recognized and trusted by a large number of customers!