Why does the moisture content of air decrease after passing through the cooling tower of an air separation plant

Why does the moisture content of air decrease after passing through the cooling tower of an air separation plant
Nov 02, 2023
Author: DEAR AST

For low-pressure air separation devices, the absolute pressure of compressed air discharged from the air compressor is around 0.6MPa. After compression, the moisture content per unit volume of air increases, causing its moisture content to reach the saturation level corresponding to the temperature at that time. When air flows through the air cooling tower, as the temperature decreases, the corresponding saturated moisture content decreases, and the excess part will precipitate from the gas in a liquid state. This portion of water vapor condenses into water, while releasing latent heat of condensation, which not only increases the cooling water volume but also increases the water temperature. But the temperature of the air exiting the tower decreases, so although the air comes into direct contact with water in the cooling tower, its moisture content will actually decrease.

For example, for a 3200m3/h oxygen generator, the processing air volume is 19580m3/h, and the absolute pressure of compressed air is 0.59MPa. The temperature of the air entering the air cooling tower is 50 ℃, and the temperature of the air exiting the air cooling tower is 30 ℃. In this case, the amount of water released by the air passing through the cooling tower can reach 220kg/h.

Kaifeng DEAR Air Separation is deeply rooted and practiced in the field of air separation research. It specializes in the research and development, manufacturing, and installation of various complete sets of air separation equipment, and is good at providing customers with the most competitive air separation project design solutions. It has been recognized and trusted by a large number of customers!

DEAR Air Separation Solve YourWhy does the moisture content of air decrease after passing through the cooling tower of an air separation plantYou can also learn about otherBiogas purification FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
When the main condenser evaporator leaks seriously, a large amount of high-pressure nitrogen will leak to the low-pressure oxygen side, and the pressure of the upper and lower columns and the purity of the product will change significantly until normal production cannot be maintained. When the main condenser evaporator leaks slightly, the pressure of the upper and lower columns will not change significantly, and the purity of liquid oxygen in the main condenser evaporator will not decrease significantly. The common phenomenon is that the purity of the gas and liquid oxygen in the main condensing evaporator is very different, and the gas concentration is lower than that in equilibrium with liquid oxygen. For example, the concentration of liquid oxygen is 99% and that of gaseous oxygen is 96%, that 7 main cooling pipes were found to be leaking during maintenance. The common causes of leakage are as follows: 1. Pipes are worn due to mutual vibration. For long tube condensing evap
2025.11.25
How to prevent scaling of cooling system of air separation equipment?
2025.11.24
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top