Construction requirements for fractionator foundation

Construction requirements for fractionator foundation
Aug 30, 2023
Author: DEAR AST
Question Reply
  1. The cold box foundation is composed of foundation body, water baffle, cold insulation layer and surface layer.

 

  1. The surface of fractionator foundation after completion shall meet the following requirements:
  2. a) There should be no cracks and other defects on the surface;
  3. b) The surface should be clean,and no inflammable materials such as wood board and linoleum are allowed to be carried;
  4. c) Surface flatness < 5 / 1000;
  5. d) The surface levelness is less than 5 / 1000, and the total length shouldnot be more than 15mm.

 

  1. After the foundation is qualified, mark the installation center line of the container according to the installation position of the vessel, and mark the direction and position of the pipe orifice.
DEAR Air Separation Solve YourConstruction requirements for fractionator foundationYou can also learn about otherLarge air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Generally, the actual cooling capacity of expander is always less than the theoretical cooling capacity. Under the same inlet and outlet pressure and inlet gas temperature, the lower the efficiency of expander, the smaller the unit refrigerant cooling capacity and the smaller the temperature drop efficiency of expander. The efficiency of expander depends on the size of various losses inside the expander. Due to the existence of various losses, the ability of gas to do external work is reduced in varying degrees. To sum up, the losses mainly include the following aspects: 1. When the air flow passes through the work wheel and the deflector, the loss caused by friction and air flow impact on the runner surface is called flow loss. 2. When the impeller is rotating, the friction heat generated by the gas around the wheel disc will increase the temperature of the gas, which is called friction blast loss. 3. When the gas passes through the deflector, the leakage from the gap bet
2025.11.07
The principle and function of molecular sieve purification system in air separation equipment?
2025.11.06
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top