What are the requirements of the air separation plant for the quality of cooling water?

What are the requirements of the air separation plant for the quality of cooling water?
Apr 21, 2023
Author: DEAR AST
Question Reply

Air separation equipmentGenerally, rivers, lakes or underground water are used as cooling water. This kind of water usually contains suspended solids (sediment and other dirt) and calcium, magnesium and other heavy carbonate [-Ca (HCO3)2And Mg (HCO3)2], Called hard water. When there are many suspended substances, it is easy to block the passage, filter screen, Valve and so on of the cooler. Calcium carbonate, magnesium and other heavy carbonate are easy to generate calcium carbonate, magnesium carbonate (MgCO) when the water temperature rises3) Sediment, that is to form the commonly called scale. Generally, when the water temperature is above 45℃, scale will begin to form, and the higher the water temperature is, the easier it is to scale. The scale attaches to the tube wall of the cooler, the stuffing of nitrogen-water precooler, nozzle or sieve hole, which not only affects the heat transfer and reduces the cooling effect, but also hinders the circulation of cooling water or air, in severe cases, equipment failure will be caused, for example, nitrogen water precooler with water will freeze the cooler (or switching heat exchanger. Scale hard, attached to the wall is not easy to clear. Therefore, cooling water is better to be softened. It is relatively simple and effective to use the magnetic device for softening treatment. Sedimentation tank should be set for removing suspended solids. If the cooling water is recycled, it is beneficial to the softening of water quality, but it covers a larger area and has a larger infrastructure investment.

For cooling water of compressor, the temperature is generally required not to be higher than 28℃, and the drainage temperature is less than 40℃. Requirements for water quality:

PH value 6.5 ~ 8.0
  
The suspended matter content is not more than 50 mg/L

Temporary hardness is not more than 17 °dh

Oil content less than 5 mg/L

Chloride ion (C1-) (Mass score) less than 50 × 10-6

Sulfate radical (SO4-2) (Mass score) less than 50 × 10-6 

The water supply and drainage of nitrogen water precooling system is independent circulation system. Because the temperature rise of cooling water in the Tower is high, the drainage temperature is high, and the scale is serious, it is required that the supplement water of this system should use low hardness water or soft water as much as possible, and its temporary hardness should generally be no more than 8.5 ° dH, other requirements are the same as compressor cooling water.

The lubricating water of the cylinder of the high pressure oxygen compressor used for filling bottles should be distilled water or soft water.

DEAR Air Separation Solve YourWhat are the requirements of the air separation plant for the quality of cooling water?You can also learn about otherLiquefied air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Test process of stainless steel pipe in air separation unit
2024.12.20
Pressure swing adsorption and temperature swing adsorption of molecular sieve
2024.12.19
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top