当前位置: Home / Faq / Large air separation FAQ /

Analysis on the cause of overproof of carbon monoxide in molecular sieve adsorber outlet of air separation plant

Analysis on the cause of overproof of carbon monoxide in molecular sieve adsorber outlet of air separation plant
Aug 09, 2024
Author: DEAR AST
Question Reply

Users reported that the on-line analyzer of a 30000 grade air separation plant showed that the outlet CO₂of the molecular sieve suddenly increased from the normal value of 0.43×10-6 to 120×10-6, and the temperature difference in the expansion air channel entering the two high-pressure plate fin heat exchangers began to expand. At the same time, the temperature in front of expander also decreased from - 105°C to - 132°C with liquid entrainment.

 

After receiving the user's notice, DEAR air separation sent technical personnel to the site for observation and detection. It was found that the location of the self-cleaning filter of the equipment was close to the chemical boundary area. When the wind direction was in the downwind direction of the chemical industry boundary area, the phenomenon that the concentration of CO₂ in the air at the inlet of the self-cleaning filter of the air compressor exceeded the standard.

 

In view of this phenomenon, the following opinions are given:

 

1.Shorten the switching cycle of molecular sieve adsorber: appropriately shorten the switching cycle of molecular sieve adsorber, shorten the time of heating, cold blowing and adsorption, and ensure that the adsorption capacity of molecular sieve is switched to the regeneration process before the adsorption capacity declining.

 

2.Regular detection ofCO₂concentration: operators use portable gas detector to detect the inlet of air filter every hour. Once the concentration of carbon monoxide in the air is found to be higher than the normal value, the air separation unit shall be operated under load reduction in time.

 

3.Load reduction operation of the plant: under the condition that the concentration of  CO₂in the atmospheric environment exceeds the standard, it is necessary to reduce the air supply volume of the air compressor, so that the total amount of carbon monoxide in the air passing through the molecular sieve adsorber will be reduced, and the air separation plant will be operated at reduced load at the same time. The normal operation of the equipment can be resumed when theCO₂concentration at the inlet of the self-cleaning filter is reduced to the normal value.

DEAR Air Separation Solve YourAnalysis on the cause of overproof of carbon monoxide in molecular sieve adsorber outlet of air separation plantYou can also learn about otherLarge air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Answer: select the small cryogenic air separation unit with argon, and give priority to verifying the real continuous operation performance of the unit with argon below 1000nm ³/h, avoiding the scheme with only drawings and no long-term operation record. Key dimensions of model selection: 1. operation performance: it is confirmed that the manufacturer has a long-term stable production case of small flow air separation with argon. Deere air separation small-scale hydrogen free total distillation argon extraction air separation, supports scale customization below 1000nm ³/h, and is equipped with intelligent control system, with mature landing performance. 2. power consumption per unit liquid argon
2026.11.06
Answer: the default unit gauge pressure is MPa (g), and the mainstream is cryogenic full low pressure external compression process. Design pressure of conventional energy-saving models in the industry: 0.50~0.55 MPa (g); The lower limit of stability of ordinary process is about 0.45 MPa (g). In general, it is not recommended to be lower than 0.42 MPa (g) for a long time in the conventional scheme. If the pressure is too low, there will be risks such as poor heat exchange in the precooling tower, insufficient purification of molecular sieve, difficult to balance the cooling capacity, and the air compressor close to the surge area. The internal compressed air is distributed with a booster. The main air compressor is mostly 0.55~0.65 MPa (g), and the lower limit is mostly 0.50 MPa (g), which is difficult to achieve below 0.45MPa (g). Deere air separation ultra-low discharge pressure patented energy-saving external compression air separation, through the collaborative optimization of the w
2026.11.06
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top