当前位置: Home / Faq / Large air separation FAQ /

Daily management of circulating water system in large air separation units

Daily management of circulating water system in large air separation units
Apr 11, 2022
Author: DEAR AST

1.Operators should adjust the discharge volume in time so that the concentration times are within the index.

2.Every week, a large amount of sewage should be discharged once. Discharge the sewage from the drainage pipe at the bottom of the tower.

3.Regularly analyse the calcium loss rate. Calcium loss rate is used to assess the system scaling situation, in general, calcium loss rate ≤ 20%.

4.Monitor the cooling water analysis once a week. Main analysis items: pH, conductivity, total phosphorus, total iron, total hardness, total alkalinity, etc. Record the daily dosing, water replenishment, drainage and chemical analysis.

5.Control index water treatment standards (international): carbon steel corrosion rate ≤ 0.125mm/a: copper corrosion rate ≤ 0.005mm/a: fouling thermal resistance ≤ 1 × 10K/W. Process control index: pH ≤ 9.2: turbidity ≤ 15.0mg/L; conductivity ≤ 2000μs/cm; total iron ≤ 1.0mg; total phosphorus ≥ 6.0mg/er: calcium loss rate ≤ 20% .

Dear Air Separation always takes science and technology as the guide, and the company has 3 research centres under the design and research institute. The company has 26 senior technical titles, 70 intermediate technical titles, and a group of highly sophisticated technical research and development talents such as doctors and masters, etc. The company has a number of design experts who enjoy a reputation in the same industry in China to ensure the technical advancement of small  air separation units, large air separation units and liquid air separation plants.

 

.

梅花项目2

DEAR Air Separation Solve YourDaily management of circulating water system in large air separation unitsYou can also learn about otherLarge air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Generally, the actual cooling capacity of expander is always less than the theoretical cooling capacity. Under the same inlet and outlet pressure and inlet gas temperature, the lower the efficiency of expander, the smaller the unit refrigerant cooling capacity and the smaller the temperature drop efficiency of expander. The efficiency of expander depends on the size of various losses inside the expander. Due to the existence of various losses, the ability of gas to do external work is reduced in varying degrees. To sum up, the losses mainly include the following aspects: 1. When the air flow passes through the work wheel and the deflector, the loss caused by friction and air flow impact on the runner surface is called flow loss. 2. When the impeller is rotating, the friction heat generated by the gas around the wheel disc will increase the temperature of the gas, which is called friction blast loss. 3. When the gas passes through the deflector, the leakage from the gap bet
2025.11.07
The principle and function of molecular sieve purification system in air separation equipment?
2025.11.06
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top