Daily management of circulating water system in large air separation units

Daily management of circulating water system in large air separation units
Apr 11, 2022
Author: DEAR AST

1.Operators should adjust the discharge volume in time so that the concentration times are within the index.

2.Every week, a large amount of sewage should be discharged once. Discharge the sewage from the drainage pipe at the bottom of the tower.

3.Regularly analyse the calcium loss rate. Calcium loss rate is used to assess the system scaling situation, in general, calcium loss rate ≤ 20%.

4.Monitor the cooling water analysis once a week. Main analysis items: pH, conductivity, total phosphorus, total iron, total hardness, total alkalinity, etc. Record the daily dosing, water replenishment, drainage and chemical analysis.

5.Control index water treatment standards (international): carbon steel corrosion rate ≤ 0.125mm/a: copper corrosion rate ≤ 0.005mm/a: fouling thermal resistance ≤ 1 × 10K/W. Process control index: pH ≤ 9.2: turbidity ≤ 15.0mg/L; conductivity ≤ 2000μs/cm; total iron ≤ 1.0mg; total phosphorus ≥ 6.0mg/er: calcium loss rate ≤ 20% .

Dear Air Separation always takes science and technology as the guide, and the company has 3 research centres under the design and research institute. The company has 26 senior technical titles, 70 intermediate technical titles, and a group of highly sophisticated technical research and development talents such as doctors and masters, etc. The company has a number of design experts who enjoy a reputation in the same industry in China to ensure the technical advancement of small  air separation units, large air separation units and liquid air separation plants.

 

.

梅花项目2

DEAR Air Separation Solve YourDaily management of circulating water system in large air separation unitsYou can also learn about otherLarge air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
The raw air is compressed to about 0.52Mpa by the air compressor after filtering out dust and impurities, and then cooled to about 10℃ by the refrigerant glycol aqueous solution or Freon, and then enters the purification system to purify and remove water, carbon dioxide and other impurities in the air. Part of the raw material air enters the lower tower via the second raw material air pipeline, another part is liquefied into liquid air via the liquefier and enters the lower tower via the liquid ...
2025.12.04
Generally, the main reason for the vibration of piston type oxygen compressor is the action of alternating load. There are two kinds of alternating loads: one is the unbalanced inertia force, the other is the interference force caused by the strong gas pressure pulse in the gas pipeline caused by the discontinuous gas supply of the compressor. The vibration caused by unbalanced inertia force can be eliminated and reduced from the structure of the machine itself. The specific methods are as follows: reasonably arrange the crank stagger angle; properly select the mass configuration of reciprocating parts. In addition, the basic design and manufacturing process of the compressor should also strictly comply with the technical specifications. For the vibration caused by air flow pressure pulse, a buffer can be installed near the cylinder exhaust pipe nozzle; the appropriate installation position of orifice plate should be selected on the gas flow channel; the shock absorber should be
2025.12.03
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top