Daily management of circulating water system in large air separation units

Daily management of circulating water system in large air separation units
Apr 11, 2022
Author: DEAR AST

1.Operators should adjust the discharge volume in time so that the concentration times are within the index.

2.Every week, a large amount of sewage should be discharged once. Discharge the sewage from the drainage pipe at the bottom of the tower.

3.Regularly analyse the calcium loss rate. Calcium loss rate is used to assess the system scaling situation, in general, calcium loss rate ≤ 20%.

4.Monitor the cooling water analysis once a week. Main analysis items: pH, conductivity, total phosphorus, total iron, total hardness, total alkalinity, etc. Record the daily dosing, water replenishment, drainage and chemical analysis.

5.Control index water treatment standards (international): carbon steel corrosion rate ≤ 0.125mm/a: copper corrosion rate ≤ 0.005mm/a: fouling thermal resistance ≤ 1 × 10K/W. Process control index: pH ≤ 9.2: turbidity ≤ 15.0mg/L; conductivity ≤ 2000μs/cm; total iron ≤ 1.0mg; total phosphorus ≥ 6.0mg/er: calcium loss rate ≤ 20% .

Dear Air Separation always takes science and technology as the guide, and the company has 3 research centres under the design and research institute. The company has 26 senior technical titles, 70 intermediate technical titles, and a group of highly sophisticated technical research and development talents such as doctors and masters, etc. The company has a number of design experts who enjoy a reputation in the same industry in China to ensure the technical advancement of small  air separation units, large air separation units and liquid air separation plants.

 

.

梅花项目2

DEAR Air Separation Solve YourDaily management of circulating water system in large air separation unitsYou can also learn about otherLarge air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
The load adjustment range of low pressure small air separation unit is related to the adjustment performance of the raw material compressor, the adjustment performance of the expander, the structural characteristics of the distillation tower and other factors. At present there are imported guide vane of the turbine air compressor flow adjustment range in 75-100%; adjustable nozzle of the turbine expander adjustment range can be in 65-100%. When oxygen is rich and the need to reduce oxygen produc...
2026.09.24
Causes of low air compressor efficiency of small air separation unit   There are many reasons for the low efficiency of air compressors, the common ones are: increase in suction temperature at any level, cooler leakage, decrease in grid frequency or voltage, blockage or increase in resistance of the compressor intercooler, gas leakage due to poor sealing, blockage or increase in resistance of the air filter, blockage or increase in resistance of the pipeline of the air separation equipmen...
2026.09.23
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts