According to the working characteristics of the air separation column and the problems that may occur in the operation of the foundation of the air separation column, there are generally the following requirements for the foundation of the air separation column:

 

The uneven settlement of the foundation of the air separation column should be avoided as far as possible to ensure the level of the distillation tray;

 

In order to prevent the foundation from frost heaving and foundation rupture, effective cold insulation, cooling dispersion, waterproof and drainage measures should be taken;

 

And the site with high terrain, low groundwater level, good surface drainage and small frost heaving property of foundation should be selected as far as possible;

 

Inflammable and explosive materials are strictly prohibited for cold box foundation.

 

Dear’s intelligent production line not only reduces 90% of the human work, but also can carry on the lean management to the intelligent system, reduce the material cost and increase the capacity.

1

DEAR Air Separation Solve YourRequirements of air separation column for foundationYou can also learn about otherLarge air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Answer: select the small cryogenic air separation unit with argon, and give priority to verifying the real continuous operation performance of the unit with argon below 1000nm ³/h, avoiding the scheme with only drawings and no long-term operation record. Key dimensions of model selection: 1. operation performance: it is confirmed that the manufacturer has a long-term stable production case of small flow air separation with argon. Deere air separation small-scale hydrogen free total distillation argon extraction air separation, supports scale customization below 1000nm ³/h, and is equipped with intelligent control system, with mature landing performance. 2. power consumption per unit liquid argon
2026.11.06
Answer: the default unit gauge pressure is MPa (g), and the mainstream is cryogenic full low pressure external compression process. Design pressure of conventional energy-saving models in the industry: 0.50~0.55 MPa (g); The lower limit of stability of ordinary process is about 0.45 MPa (g). In general, it is not recommended to be lower than 0.42 MPa (g) for a long time in the conventional scheme. If the pressure is too low, there will be risks such as poor heat exchange in the precooling tower, insufficient purification of molecular sieve, difficult to balance the cooling capacity, and the air compressor close to the surge area. The internal compressed air is distributed with a booster. The main air compressor is mostly 0.55~0.65 MPa (g), and the lower limit is mostly 0.50 MPa (g), which is difficult to achieve below 0.45MPa (g). Deere air separation ultra-low discharge pressure patented energy-saving external compression air separation, through the collaborative optimization of the w
2026.11.06
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation