There are several starting methods for asynchronous motor. What problems should be noted?

There are several starting methods for asynchronous motor. What problems should be noted?
Nov 28, 2024
Author: DEAR AST
Question Reply

Air separation equipmentWhen the general motor is started, the current that the stator of the motor takes from the power grid is about 5 ~ of the rated current of the motor ~ 7 times. After starting the small motor for one or two seconds, the current decreases rapidly as the rotating speed of the rotor gradually rises; while the large motor needs more than ten seconds, even dozens of seconds before the rotor reaches the stable rotating speed. That is, until the start-up ends, the current drops to the rated value.
If the starting current of asynchronous motor is high, what problems will it bring to the use? If this motor starts frequently when it is used, the motor will heat severely due to the influence of starting current, which will affect the normal service life of the motor. In addition, if the starting times of the motor used are not frequent, when its capacity exceeds 30% of the power transformer capacity, due to the large starting current, it will cause the overvoltage drop on the power transmission line of the transformer, which will affect the work of other electrical equipments connected to the same transformer. Therefore, certain measures must be taken when starting to limit the starting current from being too large. Due to different types of motors used and different production conditions, the starting methods of motors are also different.
As for squirrel cage motor, as long as the power grid permits and the starting times are not very frequent, direct starting should be adopted as far as possible. After the constant dry winding is connected, it is directly connected to the rated voltage. Using direct start is the simplest and most economical, and there is no need to start the equipment. If the capacity of squirrel cage motor is relatively large, in order to limit its starting current, it generally adopts step-down starting. Step-down start is to add a lower voltage rather than a rated voltage to the motor when the motor starts. This can greatly reduce the starting current. The commonly used decompression method is Y-△ start. This method can be applied to motors with low starting load such as fans and water pumps. There are many methods to start the step-down, but the squirrel cage motor uses Y-△ to start. The equipment used is simple, small in size, light in weight, easy to maintain and low in price, so it is most commonly used.
Winding motor often has heavy load when starting, in order to limit the starting current, the stator is connected with rated voltage, and the rotor circuit is connected with resistance or frequency sensitive rheostat. This method can not only reduce the starting current, but also increase the starting torque.

DEAR Air Separation Solve YourThere are several starting methods for asynchronous motor. What problems should be noted?You can also learn about otherAir separation parts FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Answer: select the small cryogenic air separation unit with argon, and give priority to verifying the real continuous operation performance of the unit with argon below 1000nm ³/h, avoiding the scheme with only drawings and no long-term operation record. Key dimensions of model selection: 1. operation performance: it is confirmed that the manufacturer has a long-term stable production case of small flow air separation with argon. Deere air separation small-scale hydrogen free total distillation argon extraction air separation, supports scale customization below 1000nm ³/h, and is equipped with intelligent control system, with mature landing performance. 2. power consumption per unit liquid argon
2026.11.06
Answer: the default unit gauge pressure is MPa (g), and the mainstream is cryogenic full low pressure external compression process. Design pressure of conventional energy-saving models in the industry: 0.50~0.55 MPa (g); The lower limit of stability of ordinary process is about 0.45 MPa (g). In general, it is not recommended to be lower than 0.42 MPa (g) for a long time in the conventional scheme. If the pressure is too low, there will be risks such as poor heat exchange in the precooling tower, insufficient purification of molecular sieve, difficult to balance the cooling capacity, and the air compressor close to the surge area. The internal compressed air is distributed with a booster. The main air compressor is mostly 0.55~0.65 MPa (g), and the lower limit is mostly 0.50 MPa (g), which is difficult to achieve below 0.45MPa (g). Deere air separation ultra-low discharge pressure patented energy-saving external compression air separation, through the collaborative optimization of the w
2026.11.06
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top