What are air-opening and air-closing membrane control valves in small air spearation unit?

What are air-opening and air-closing membrane control valves in small air spearation unit?
Feb 28, 2022
Author: DEAR AST

When there is no pressure signal input, the valve is closed; when there is a pressure signal, the valve starts to open, and the larger the input signal, the larger the valve opening, this kind of film regulating valve is called air-opening film regulating valve in small air spearation unit.

When there is no pressure signal input, the valve is fully open, and when there is a pressure signal input, the valve starts to close; the larger the input signal, the smaller the valve opening; when the input signal reaches the maximum, the valve is fully closed, this film valve is called gas-closed film adjustment valve.

In practice, the choice of gas open, gas closed mainly from the production of safety requirements to consider, the regulating valve is closed to the production of the smallest hazard, the choice of gas open type. If the valve is open when the least harmful, to choose the gas-closed type. Liquid-air-liquid nitrogen control valve, turbine expansion machine in front of the emergency shut-off valve are gas-open type. When the gas is cut off, the valve is in a closed state; turbomachine anti-surge valve in the gas cut off, the valve must be open, using gas-closed type. The venting valve on the oxygen storage tank and the nitrogen venting valve on the upper tower are gas-closed, so that in the event of a failure, power and gas outages can be bled to ensure safety.

In the design process, Dear Air has designed all aspects of technology, piping and valves to meet the international standards of the industry to ensure high quality requirements for small air spearation unit, large air spearation unit and liquid air spearation plant installation.

山东临沂钢铁集团(三德)-16000

DEAR Air Separation Solve YourWhat are air-opening and air-closing membrane control valves in small air spearation unit?You can also learn about otherSmall air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Generally, the actual cooling capacity of expander is always less than the theoretical cooling capacity. Under the same inlet and outlet pressure and inlet gas temperature, the lower the efficiency of expander, the smaller the unit refrigerant cooling capacity and the smaller the temperature drop efficiency of expander. The efficiency of expander depends on the size of various losses inside the expander. Due to the existence of various losses, the ability of gas to do external work is reduced in varying degrees. To sum up, the losses mainly include the following aspects: 1. When the air flow passes through the work wheel and the deflector, the loss caused by friction and air flow impact on the runner surface is called flow loss. 2. When the impeller is rotating, the friction heat generated by the gas around the wheel disc will increase the temperature of the gas, which is called friction blast loss. 3. When the gas passes through the deflector, the leakage from the gap bet
2025.11.07
The principle and function of molecular sieve purification system in air separation equipment?
2025.11.06
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top