What are the reasons for the poor cooling effect of cooler? How to deal with it?

What are the reasons for the poor cooling effect of cooler? How to deal with it?
Sep 09, 2022
Author: DEAR AST
Question Reply

1) insufficient cooling water. The heat of the air is not enough to be taken away by the cooling water, resulting in the increase of the next level of suction temperature, the decrease of gas density, and finally the reduction of exhaust volume. Therefore, the water supply pressure of cooling water should be closely monitored during operation to control the water supply. The process generally requires that the cooling water pressure should be greater than 0.15MPa (surface pressure );

2) cooling water temperature is too high. High water temperature reduces the temperature difference between water and gas, and reduces the effect of heat and cooling. Even if the amount of cooling water is not reduced, the temperature will still be very high after gas cooling;

3) There are too much scale in the cooling water pipe or it is blocked by sediment and organic matter, as well as moisture precipitation after cooling on the air side of the cooler, which can not be discharged timely, all of which will affect the heat transfer area or the heat transfer working condition, and affect the cooling effect. The cooling effect is not good, which makes the temperature of the next level rise, affects the performance curve of the next level, and reduces the outlet pressure and flow. Figure 98 shows the change of the performance curve of a compressor obtained from the experiment when the temperature of cooling water rises from 10℃ to 30℃. In addition, when the suction volume of the lower level is reduced, it will cause that the air produced by the former level can not be "eaten in" completely, and it is easy to make the work of the former level enter into the surge area, and surge occurs at this level. Treatment methods include: check the temperature and pressure of the upper water and make adjustments; if the temperature and pressure of the upper water are normal, stop and disassemble to check, use physical and chemical methods to clean or replace the cooler; if the cooler leaks, replace the cooler.

DEAR Air Separation Solve YourWhat are the reasons for the poor cooling effect of cooler? How to deal with it?You can also learn about otherAir separation parts FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
Liquid air separation plant solutions Most liquid air separation plant cold energy receiving stations have a peaking role, their use is generally for domestic gas or car refuelling, with high and intermittent periods of gas consumption, for example 1-2 hour peaks in the morning and midnight. If the liquid air separation plant vapourisation plant is intermittent, the plant will not operate continuously. The solution is based on the intermittent use of liquid air separation plant and is character...
2026.07.08
In the main column of the air separation column, the distribution of argon varies with the position of the liquid air inlet. With the increase of liquid air inlet position, the maximum concentration of argon enrichment zone in the stripping section also increases, and the nitrogen content in the distillate can be reduced. However, the argon content in the downstream also increases. In order to ensure the purity of oxygen, more trays are needed under the extraction port of argon fraction. Therefore, in the case of producing argon, the position of liquid air supply E1 should be appropriately increased compared with the case of not producing argon. Some unit is equipped with two liquid air inlet positions to meet the conditions of argon production and non argon production respectively. In the production of argon, in order to improve the extraction rate of argon, the content of argon in oxygen and nitrogen must be reduced. When the content of argon in exhaust nitrogen is more than 0.3%
2026.07.07
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top