The actual running current of 132kw-8 electric motor is 220A ~ 240A, 4-tableAir compressorShare An air storage tank, and the actual pressure required is 0.6 ~ 0.7Mpa, remote pressure gauge indication is 0.64Mpa. How to reform?

One, four setsAir compressorChange only one (132kw-8) Auxiliary with a pressure transmitter, and feed back the actual pressure of the sampling pipe network to the inverter. Inverter automatically adjusts output voltage through software (PID function. (That is to reduce the actual power) to meet the actual gas consumption. After agreement, in order not to affect the motor temperature, we adopt RB600-3P160G type (160kw inverter ).

II. Adopt manual switching of power/frequency conversion. If there is something wrong with the frequency converter, it can be changed to power frequency operation. It really does not affect the actual production of the factory, ensureAir compressorLong-term operation.

Third, according to the requirements of customers' pressure, the network management pressure can be set to 0.6Mpa, because there are fourAir compressorAt the same time, we will save the electric energy wasted by the three unmodified ones through the one converted by frequency conversion.

IV. According to the practical experience, the rebuilt inlet current is about 190A, and the saving power is about 30/2 = 15kw. Power = kilowatt/hour (namely 15 degrees/hour), running in 24 hours, saving power per day = 15*24 = 360 degrees. Calculate by 0.5 yuan per degree = 360*0.5 = 180 yuan/day. Monthly = 180*30 = 5400 yuan.

V. Benefits after frequency conversion transformation of air compressor:

1. Save Energy; 2. Reduce the operating cost; 3. Increase the precision of pressure; 4. Extend the service life of compressor; 5. LowerAir compressorNoise

DEAR Air Separation Solve YourMethod of reforming air compressorYou can also learn about otherLarge air separation FAQ about DEAR Air Separation, and solve the problem for you.
Didn’t find the problem encountered?
Please contact live chat or email for quick help.
Related FAQ
More Related FAQ
1. Before filling with pearlite, the water accumulated on the foundation surface of air separation unit must be removed, dried with hot air, and all manholes shall be closed. 2. When filling pearlite, all containers and pipes in the cold box should be inflated and kept at 50kPa pressure, then slightly open the valve of each meter pipeline, and all thermometers should be electrified to check whether the thermometer cable is damaged during the filling process. 3. The filled pearlite shall not be mixed with combustibles. 4. When filling with pearlite, coarse mesh or pearlite pouring device should be set at the manhole on the top of the cold box to prevent whole bag pearlite from entering the cold box. 5. After the pearlite is filled, the manhole shall be sealed.
2026.08.18
What is the oxygen extraction rate?
2026.08.17
Need more information?
Contact us for more details about our air separation equipment, solutions and services.
Products
  • Large air separation
  • Small air separation
  • High purity nitrogen air separation
  • Liquefaction air separation
  • Complete air separation
  • Biogas purification
  • Air separation parts
Need more information?
Tel:+86-19837850537
© Kaifeng DEAR Air Separation Industry Co., Ltd.. All rights reserved.
Online
Inquiry
Email
Top